Infrastructure A home for your servers, services!

Building

Address: 1108 Budapest, Kozma u. 2.
Full size of the machine room: 1,500 m².
False floor load bearing capacity: point-like: 50 kN/m².
Machine room’s full ceiling height: 3.7 metres.
Fire protection class: 60 minutes.
Availability of the power and air conditioning systems: 99.999%.
Redundancy of the heating, ventilation and air conditioning (HVAC) systems: at least N+1.

Telecom Connections

Two independent fibre optic communication links and a microwave connection to Invitel’s infrastructure.
Additional optical fibres to connect customers through fibre optic connections.
Direct connections to the main Internet nodes (e.g. Invitel’s Ilka Street DataCenter, BIX, Infopark, Dataplex, etc.).
A radio connection can be set up for communication with the DataCenter.
A 3x10 Gbit/sec redundant connection to Invitel’s other sites.

Security

24/7 security service.
Closed-chain IP video monitoring and recording system, covering the full area and the vicinity of the facility.
Continuously managed access control and intrusion detection system.
Continuously managed facility management system.
The machine rooms are protected against conducted and radiated electromagnetic disturbances (EMC).
Early Warning Smoke Detection System c/w aspiration and optical detectors.
The delay between detection and the star of suppression is 30 seconds.
Fire suppression system with FM-200 (HFC-227ea) fire suppression gas.

Power supply and cooling

Availability of the power and air conditioning systems: 99.999%.
3 medium-voltage power feed connections, each with a current carrying capacity of 1,600 kVA (2 operating, 1 standby).
2+2 1400 kVA Cummins Power Generation generators in 2 diesel groups, in tandem mode.
Under full load, the systems can back up 72 hours of power loss.
2N UPS system, with a configuration of 3 + 1 on either side, offering a performance of 1650 kVA + 550 kVA, to ensure power availability between the start of power loss and the full run-up of generators.
Under full load, the system can back up 30 minutes of power loss.
A + B independent UPS in the machine rooms.
1600 kW cooling performance with a redundancy of 2N.
Energy efficient cooling solutions (a combination of free cooling condensers and compact liquid chillers).
40 indoor computer air conditioners, each offering a performance of 50 kW, c/w humidification, with a configuration of N+2 in each machine room.
Air handling equipment to provide the facility with fresh, dust-free, cooled/heated air.